Analog I/O

This group of parameters contains the programming options for analog drive inputs/outputs.

[Anlg In 0 Lo]
[Anlg In 1 Lo]
[Anlg In 2 Lo]

Sets the percentage of voltage or current from Input 0, 1
or 2 that represents [Minimum Freq].

Parameter Number

237, 239, 248

Parameter Type

Read and Write

Display Units / Drive Units

0.1% / 920 = 100%

Factory Default

0.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[Anlg In 0 Hi]
[Anlg In 1 Hi]
[Anlg In 2 Hi]

Sets the percentage of voltage or current from Input 0, 1
or 2 that represents [Maximum Freq].

Parameter Number

238, 240, 249

Parameter Type

Read and Write

Display Units / Drive Units

0.1% / 920 = 100%

Factory Default

100.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[Analog Trim En]

This parameter enables Analog In 0 as a trim input. Setting
this parameter to “Enable” creates a trim signal to the ac-
tive frequency source at Analog In 0. The trim value is

±

10% of [Maximum Freq].

Minimum Input = –10% Trim
Mid-Point Input = No Trim
Maximum Input = +10% Trim

Parameter Number

90

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Anlg Signal Loss]

Selects the drive reaction to a loss of analog input
signal. This signal could represent commanded fre-
quency, PI feedback, or others.

Bits 0-2 define the input as a pot with wiper loss
detect and will generate an “Open Pot Fault” (F09).

Bits 3-5 define the input as offset (4mA, 2V) with loss
detect below that value (see below).

Parameter Number

250

Parameter Type

Read and Write

[4-20mA Loss Sel]

This parameter selects the drives response to a loss of
analog input signal (input below 2V or 4mA). Requires that
the loss selection bits for [Anlg Signal Loss] be set to “1.”
This function is active only when the input is configured
in [Freq Select 1/2], [PI Ref Select], [PI Fdbk Select].

Important: Depending on the type of input configuration
(i.e. Frequency or PI), the resultant action will vary (see
“Action” column at right).

When configured in [PI Ref Select] or [PI Fdbk Select], only
the alarm and fault conditions will occur. The drive will not
perform a speed change.

Parameter Number

150

Parameter Type

Read and Write

Factory Default

“Min/Alarm”

Units

Display

Drive Action

“Min/Alarm” 0

Freq - Drive outputs [Minimum Freq] and issues an alarm.

PI - Alarm issued.

“Stop/Fault”

1

Freq - Drive stops and issues “Hertz Err Fault”.

PI - Drive stops and issues “Hertz Err Fault”.

“Hold/Alarm”

2

Freq - Drive maintains last output freq & issues an alarm.

PI - Alarm issued.

“Max/Alarm”

3

Freq - Drive outputs [Maximum Freq] and issues an alarm.

PI - Alarm issued.

“Pre1/Alarm”

4

Freq - Drive outputs [Preset Freq 1] and issues an alarm.

PI - Alarm issued.

Bit 7 Bit 6 Bit 5

Bit 4 Bit 3 Bit 2

Bit 1 Bit 0

Input 0 Signal Loss for Pot – 1=Yes, 0=No
Input 1 Signal Loss for Pot – 1=Yes, 0=No
Input 2 Signal Loss for Pot – 1=Yes, 0=No
Input 0 Signal Loss for 4-20mA/2-10V – 1=Yes, 0=No
Input 1 Signal Loss for 4-20mA/2-10V – 1=Yes, 0=No
Input 2 Signal Loss for 4-20mA/2-10V – 1=Yes, 0=No
Not Used
Not Used