Motor control, Control select, Flux amps ref – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 139

Advertising
background image

Programming

6–57

Motor

Control

This group of parameters defines basic motor control.

[Control Select]

Selects the motor control method for the drive. The default
setting provides full stator flux control that is suitable for
most applications.

Important: When using synchronous motors, [Control Se-
lect] must be set to V/Hz operation (“Fixed Boost” or “Full
Custom”).

Additional selections are offered to optimally tune
performance:
• Two volts/Hertz modes are available; one using simple

voltage boost and one for complete configurability.
These may be required for special motors or unmatched
multi-motor installations.

• The Economize mode offers all the advantages of stator

flux control plus the added feature of an “auto-econo-
mizer.” If a motor remains lightly loaded, the drive will
reduce output voltage (and therefore output kW) in or-
der to reduce the energy (operating) costs of the lightly
loaded motor. This can result in up to 20% kW savings.

Parameter Number

9

Parameter Type

Read and Write

Factory Default

“Sens Vector”

Units

Display Drive

“Economize” 0

Stator Flux control with Economize

“Sens Vector” 1

Stator Flux control

“Fixed Boost” 2

V/Hz w/programmed accel/run boost

“Full Custom” 3

V/Hz with full configuration

Full Custom

Fixed

Default

Voltage

0

0

Frequency

Factory Default

Motor Rated

and

Maximum

Motor Rated

and

Maximum

Base/Maximum Voltage
Base/Maximum Frequency

Voltage

0

0

Frequency

Run Boost

Start Boost

B

A

Base Voltage

Base Frequency

Voltage

0

0

Frequency

Motor Rated

Maximum

Start Boost

Break Voltage
Break Frequency

Maximum

Base Voltage

Base Frequency

Maximum Voltage
Maximum Frequency

Motor Rated

Run Boost

[Flux Amps Ref]

Used in “Economize” & “Sens Vector” modes - Sets the
value of amps required to maintain full motor flux. If set to
zero, the drive will use an internal value based on [Motor
NP Amps] and drive kW (HP). Refer to Chapter 5 for setup
information.

Parameter Number

192

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Amp / 4096 = Drive Rated Amps

Factory Default

0.0 Amps

Minimum Value

0.0 Amps

Maximum Value

75.0% of Drive VT Rated Amps