[Overload Amps]

This value should be set to the motor nameplate Full Load
Amps (FLA) for 1.15 SF motors. For 1.0 SF motors the
value should be set to 0.9 x nameplate FLA.

Parameter Number

38

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Amps / 4096 = Rated Amps

Factory Default

115% of Drive Rating

115.0% of Drive Rating Firmware 5.001 & later

Minimum Value

20% of Drive Rated Amps

0.0% of Drive Rated Amps Firmware 5.001 & later

Maximum Value

115% of Drive Rated Amps

115.0% of Drive Rated Amps Firmware 5.001 & later

[VT Scaling]

This parameter scales the drive for VT ampere ratings.

Important: This parameter must be set to “Disabled” when
drive is used in a fibers application.

This parameter cannot be changed while the drive is
running.

Parameter Number

203

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

Disables Variable Torque Scaling

“Enabled” 1

Enables Variable Torque Scaling

[Motor NP RPM]

This value should be set to the motor nameplate rated
RPM.

This parameter cannot be changed while the drive is
running.

Parameter Number

177

Parameter Type

Read and Write

Display Units / Drive Units

1 RPM / 1 RPM

Factory Default

1750 RPM

Minimum Value

60 RPM

Maximum Value

24000 RPM

[Motor NP Hertz]

This value should be set to the motor nameplate rated
frequency.

This parameter cannot be changed while the drive is
running.

Parameter Number

178

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 10

Factory Default

60 Hz

Minimum Value

1 Hz

Maximum Value

400 Hz

[Motor NP Volts]

This value should be set to the motor nameplate rated
volts.

This parameter cannot be changed while the drive is
running.

Parameter Number

190

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

Drive Rated Volts

Minimum Value

0 Volts

Maximum Value

2 x Drive Rated Volts

[Motor NP Amps]

This value should be set to the motor nameplate rated
current.

This parameter cannot be changed while the drive is
running.

Parameter Number

191

Parameter Type

Read and Write

Display Units / Drive Units

1 Amp / 4096 = Drive Rated Amps

Factory Default

Drive Rated Amps

Minimum Value

0 Amps

Maximum Value

2 x Drive Rated Amps