Encoder freq, Pulse freq, Mop freq – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 88: Heatsink temp, Power ol count, Motor ol count, Last fault, Metering

Advertising
background image

6–6

Programming

Metering

[Encoder Freq]

This parameter displays the frequency command present
at encoder input terminals of TB3. This value is displayed
whether or not this is the active frequency command.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[Pulse Freq]

This parameter displays the frequency command present
at pulse input terminals of TB2. This value is displayed
whether or not this is the active frequency command.

Parameter Number

254

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[MOP Freq]

This parameter displays the frequency command from the
MOP. The MOP frequency command can be adjusted by
TB3 (if present) and appropriate inputs are selected (see
page

2–27

). Some SCANport adapters, including the RIO

Adapter, can also adjust the MOP frequency command.
This value is displayed whether or not this is the active
frequency command.

Parameter Number

137

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Heatsink Temp]

This parameter displays the heatsink temperature of the
drive.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

° C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

° C

[Power OL Count]

Displays the percentage of accumulated I

2

t for the drive

thermal overload protection. Running continuously above
115% of drive rated amps will accumulate a value of 100% and
generate a Power Overload Fault (F64).

Parameter Number

84

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Motor OL Count]

This parameter displays the percentage of accumulated
I

2

t for the motor overload protection. Running continuously at

programmed [Overload Amps] will accumulate approximately
70%. Reduction of load will reduce the OL count. 100% value
will generate an Overload Fault (F07).

Parameter Number

202

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Last Fault]

This parameter displays the last drive fault. It is updated
whenever a new fault occurs.

Parameter Number

4

Parameter Type

Read Only

Display Units / Drive Units

Fault Number / Fault Number

Factory Default

None

Minimum Value

None

Maximum Value

None

Frequency

Displayed

Incoming Encoder Pulse Rate

[Encoder PPR]

=

Frequency

Displayed

Incoming Pulse Rate (Hz)

[Pulse Scale]

=

Advertising