A–4

Specifications and Supplemental Information

User Supplied Enclosures

1336 PLUS II drives installed in user supplied enclosures may be mounted within an enclosure
or may be mounted to allow the heat sink to extend outside the enclosure. Use the information
below in combination with the enclosure manufacturer’s guidelines for sizing.

Cat No.

Base Derate
Amps

1

Derate
Curve

2, 3

Heat Dissipation
Drive Watts

2, 3, 4

Heat Sink
Watts

2

Total
Watts

2

200-240V DRIVES

AQF05
AQF07
AQF10
AQF15
AQF20
AQF30
AQF50
AQF75
A007
A010
A015
A020
A025
A030
A040
A050
A060
A075
A100
A125

2.3
3.0
4.5
6.0
8.0
12
18
22
27
34
48
65
77
80
120
150
180
240
291
325

Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A

No Derate

Figure B
Figure D

No Derate
No Derate
No Derate

Figure G
Figure H
Figure J
Figure L
Figure M
Figure N

13
15
17
21
25
33
42
58
156
200
205
210
215
220
361
426
522
606
755
902

15
21
32
42
56
72
116
186
486
721
819
933
1110
1110
1708
1944
2664
2769
3700
4100

28
36
49
63
81
105
158
244
642
921
1024
1143
1325
1330
2069
2370
3186
3375
4455
5002

380-480V DRIVES

BRF05
BRF07
BRF10
BRF15
BRF20
BRF30
BRF50
BRF75
BRF100
BRF150
BRF200
B015
B020
B025
B030
BX040
B040
B050
BX060
B060
B075
B100
B125
BX150
B150
B200
B250
BP/BPR250

6

BX250
B300

5

BP/BPR300

6

B350

5

BP/BPR350

6

B400

5

BP/BPR400

6

B450

5

BP/BPR450

6

B500

5

B600

5

1.2
1.7
2.3
3.0
4.0
6.0
9.0
15.4
22.0
24.0
27.0
27
34
42
48
59
65
77
77
96
120
150
180
180
240
292
325
322
360
425
357
475
421
525
471
590
527
670
670

Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A

No Derate

Figure B
Figure C
Figure D
Figure E
Figure E
Figure F
Figure F

No Derate

Figure G
Figure H
Figure J
Figure J
Figure L
Figure M
Figure N
Figure O

No Derate
No Derate

Figure P

No Derate

Figure Q

No Derate

Figure R

No Derate

Figure S
Figure T
Figure T

12
13
15
16
19
23
29
58
68
88
96
117
140
141
141
175
175
193
193
361
361
426
522
606
606
755
902
491
902
1005
619
1055
733
1295
793
1335
931
1395
1485

9
15
20
27
36
54
84
186
232
332
356
486
628
720
820
933
933
1110
1110
1708
1708
1944
2664
2769
2769
3700
4100
4658
4100
4805
5342
5455
6039
6175
6329
6875
7000
7525
8767

21
28
35
43
55
77
113
244
300
420
452
603
768
861
961
1108
1108
1303
1303
2069
2069
2370
3186
3375
3375
4455
5002
5149
5002
5810
5961
6510
6772
7470
7122
8210
7931
8920
10252

500-600V DRIVES

CWF10
CWF20
CWF30
CWF50
CWF75
CWF100
CWF150
CWF200
C025
C030
C040
C050
C060
C075
C100
C125
C150
C200
C250
CX300
C300

5

C350

5

CP/CPR350
C400

5

CP/CPR400
C450

5

C500

5

C600

5

2.4
4.8
7.2
9.6
10
12
19
24
30
35
45
57
62
85
109
138
168
252
284
300
300
350
350
400
400
450
500
600

Figure U
Figure U
Figure U
Figure U
Figure U
Figure U
Figure U
Figure U

No Derate
No Derate
No Derate
No Derate
No Derate

Figure G
Figure I
Figure K
Figure V
Figure W
Figure X
Figure Y
Figure AB

&

AC

Figure AB

&

AC

Figure Z
Figure AB

&

AC

Figure AA
Figure AB

&

AC

Figure AB

&

AC

Figure AB

&

AC

25
29
32
35
38
41
52
60
141
141
175
193
193
361
426
522
606
755
890
940
926
1000
580
1430
711
1465
1500
1610

29
57
87
117
148
177
286
358
492
526
678
899
981
1533
1978
2162
2315
3065
3625
3990
5015
5935
6125
7120
7000
8020
8925
10767

54
86
119
152
186
218
338
418
633
667
853
1092
1174
1894
2404
2683
2921
3820
4515
4930
5941
6935
6705
8550
7711
9485
10425
12377

1

Base Derate Amps are based on nominal voltage
(240, 480 or 600V). If input voltage exceeds Drive
Rating, Drive Output must be derated. Refer to

Figure AE

.

2

Rating is at 4 kHz (2 kHz for 224-448 kW/300-600
HP, 500-600V). If carrier frequencies above 4 kHz
are selected, drive rating must be derated. See

Figure A

-

AC

.

3

Drive Ambient Temperature Rating is 40

° C. If

ambient exceeds 40

° C, the drive must be

derated. Refer to

Figure A

-

AC

.

4

Drive Rating is based on altitudes of 1,000 m
(3,000 ft) or less. If installed at higher altitude,
drive must be derated. Refer to

Figure AD

.

5

Important: Two (2) 725 CFM fans are required if
an open type drive is mounted in a user supplied
enclosure.

6

Important: 1336F-BPRxxx - two (2) 450 CFM
fans are required if an open type drive is mounted
in a user supplied enclosure.