CE Conformity
C–5
Filter Mounting (continued)
1
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate. See requirements 5 & 6 on page
2
Refer to the Filter Selection table on page
for frame references and corresponding catalog numbers.
Conduit Box
1
To Motor
1
Access Panel and
Input Terminal Block
Lower Access Panel
Important: Drive and filter must be
mounted to a common back plane with a
positive electrical bond. Spacing is
determined by Conduit Box.
Three-Phase
Input
1
To Motor
1
Three-Phase
Input
1
Conduit Box
1
Nipple/Fitting
Figure C.3
1336
PLUS
II
(Through-the-Wall Mounting)
Frames D & E
2
Figure C.4
1336
PLUS
II
(Conventional Mounting)
Frames D & E
2