Programming

Encoder

Feedback

This group of parameters contains all the parameters necessary to activate encoder feed-
back for closed loop operation.

[Speed Control]

This parameter selects the type of speed modulation active
in the drive.

This parameter cannot be changed while the drive is
running.

Important: “No Control” and “Phase Lock” are the only
available options for synchronous motors.

If encoder feedback closed loop speed regulation is re-
quired, “Encoder Fdbk” must be selected.

Parameter Number

77

Parameter Type

Read and Write

Factory Default

“Slip Comp”

Units

Display Drive

“No Control” 0

Frequency regulation

“Slip Comp” 1

Slip compensation

“Speed Droop” 2

Negative slip compensation

“Phase Lock” 3

Enable phase lock to pulse input

“Encoder Fdbk” 4

Encoder feedback-closed loop

“Droop + Reg” 5

Enc. fdbk.-closed loop w/ active
droop

“P Jump” 6

Traverse function

“Process PI” 7

Closed loop PI control

[Encoder Type]

This parameter selects the feedback encoder signal type.
The drive can accept single channel (Pulse) or dual chan-
nel (Quadrature) signals.

This selection must match the type of encoder being used.
If “Pulse” is selected and a dual channel encoder is wired
(see page

2–30

), the feedback indication will be incorrect

by a factor of 2 and no direction indication will be offered.
If “Quadrature” is selected and a single channel encoder
is wired, the feedback value will always be zero.

This cannot be changed while drive is running.

Parameter Number

152

Parameter Type

Read and Write

Factory Default

“Quadrature”

Units

Display Drive

“Pulse” 0

Single channel encoder

“Quadrature” 1

Dual channel encoder

[Encoder PPR]

This parameter contains the scaling factor for encoder
feedback speed regulation. Enter the actual encoder puls-
es per revolution

Parameter Number

46

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

1024 PPR

Minimum Value

1

Maximum Value

4096

[Maximum Speed]

This Parameter sets the output frequency at full frequency
reference for:

1.Encoder feedback speed regulation.

2.All analog inputs to TB2 (remote pot, 0-10V & 0-20 mA).

NOTE: [Maximum Freq.] must be raised to allow operation
or modulation above [Maximum Speed].

Parameter Number

151

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 10

Factory Default

400 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[Motor Poles]

This parameter contains the number of motor magnetic
poles. This value translates output frequency into actual
motor RPM during closed loop operation. It is calculated
from [Motor NP Hertz] and [Motor NP RPM].

Parameter Number

153

Parameter Type

Read Only

Display Units / Drive Units

1 Poles / Poles