Installation/Wiring

2–25

Terminal Block TB2

TB2 is located at the bottom of the Main Control Board. A Frame
drives have 18 positions. Remaining frame sizes have 22 positions.
The maximum and minimum wire size accepted by TB2 is 2.1 and
0.30 mm

2

(14 and 22 AWG). Maximum torque for all terminals is

1.36 N-m (12 lb.-in.). Use Copper wire only. See

Figure 2.1

.

Terminal Block TB3

The Control Interface Option provides a means of interfacing various
signals and commands to the 1336

PLUS

II

by using contact closures.

Several different versions of the option are available:

• L4

Contact Closure Interface

1

.

• L4E Contact Closure Interface

1

with Encoder Feedback Inputs.

• L7E Contact Closure Interface

1

with Encoder Feedback Inputs

for use with encoder loss detection.

• L5

+24VAC/DC Interface.

• L5E +24VAC/DC Interface with Encoder Feedback Inputs.

• L8E +24VAC/DC Interface with Encoder Feedback Inputs

for use with encoder loss detection.

• L6

115VAC Interface.

• L6E 115VAC Interface with Encoder Feedback Inputs.

• L9E 115VAC Interface with Encoder Feedback Inputs

for use with encoder loss detection.

1

Uses internal +5V DC supply.

The user inputs are connected to the option board through TB3 (see

Figure 2.1

for location). The L4, L5 and L6 options each have nine

control inputs. The function of each input must be selected through
programming as explained later in this section. The L4E through L9E
options are similar to L4, L5 and L6 with the addition of encoder
feedback inputs. In addition, the L7E, L8E and L9E options allow
encoder loss detection. Refer to Appendix A for further information.

The maximum and minimum wire size accepted by TB3 is 2.1 and
0.30 mm

2

(14 and 22 AWG). Recommended torque for all terminals

is 0.90-1.13 N-m (8-10 lb.-in.). Use Copper wire only.

Digital Inputs

Digital inputs are connected at TB3.

Input Mode Select

A number of combinations are available by first programming
[Input Mode] to the desired control scheme (i.e. 2 wire, 3 wire or
Status). The remaining inputs can then be configured by program-
ming [TB3 Term 22 Sel] through [TB3 Term 28 Sel]. Refer to the
Digital I/O parameter group in Chapter 6 for programming
information.