[FStart Forward]

This value sets the frequency at which the forward speed
search begins. If this value exceeds [Maximum Freq],
speed search will begin at [Maximum Freq]. Forward
search ends at zero Hertz or when motor speed is found.

Parameter Number

156

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

60 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[FStart Reverse]

This value sets the frequency at which the reverse speed
search begins. If this value exceeds [Maximum Freq],
speed search will begin at [Maximum Freq]. Reverse
search ends at zero Hertz or when motor speed is found.

Parameter Number

157

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

0 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[LLoss Restart]

This parameter selects the reconnect mode after recovery
from a line loss condition.

Parameter Number

228

Parameter Type

Read and Write

Factory Default

“Track Volts”

Units

Display Drive

“Speed Search” 1

Frequency sweep

“Use Encoder” 2

Read feedback

“Track Volts” 3

Read motor volts

Firmware 5.001 & later

“Speed Srch 10s” 4

Frequency sweep takes 10 seconds

Firmware 5.001 & later

“Speed Srch 20s” 5

Frequency sweep takes 20 seconds

Firmware 5.001 & later

“Speed Srch 40s” 6

Frequency sweep takes 40 second

Drive Units=“4” Firmware 4.001 & before “Last Speed” 7

Start at last output

[Line Loss Mode]

This parameter sets the drive reaction to a loss of input
voltage and is often referred to as Inertia Ride Through.
If the drive is used to determine loss of AC input (as op-
posed to an external device), it will monitor the falling DC
bus voltage. When Vbus falls below 85% of nominal, a
“line loss” condition is issued and an alarm bit is set.

The line loss mode selected, along with [Line Loss Fault]
and [Low Bus Fault] will determine the drives response to
a loss of input.

• With this parameter set to “LoBus>Off” and . . .

[Line Loss Fault] is . . .

- Enabled a fault is issued 0.5 seconds after a “line

loss” condition.

- Disabled a fault will not be issued.

[Low Bus Fault] is . . .

- Enabled a fault is issued at the bus undervoltage

trip level.

- Disabled a fault will not be issued.

• With this parameter set to “LoBus>Decel” and [Line

Loss Fault] & [Low Bus Fault] are disabled – the drive
will decelerate the output frequency following motor
speed to create a regenerative condition that maintains
Vbus at 85% nominal. The amount of available me-
chanical energy determines the length of “ride
through.”

If this parameter = “LoBus>Off,” then [LLoss Restart] de-
termines the reconnect scheme for the motor. If this
parameter is set to “LoBus>Decel,” no reconnect scheme
is required.

Parameter Number

256

Parameter Type

Read/Write

Factory Default

“LoBus>Off”

Units

Display Drive

“LoBus>Off” 0

Turn off output on –15% Vbus

“Input>Off” 1

Not functional at time of printing.
Turns off output on
High Speed Input = True

“LoBus>Decel” 2

Regulates Vbus using deceleration
Active on –15% Vbus

“Input>Decel” 3

Not functional at time of printing.
Regulates Vbus using deceleration
Active on High Speed Input = True