Load loss level, Load loss time, Bus reg level – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 108: Max bus volts

Advertising
background image

6–26

Programming

Feature Select

[Load Loss Level]

Sets the torque current level below which a load loss fault/
warning will occur. The value is expressed as a
percentage of programmed [Motor NP Amps].

Parameter Number

291

Parameter Type

Read and Write

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

50%

Minimum Value

20%

0%

Firmware 6.001 & later

Maximum Value

100%

[Load Loss Time]

Sets the amount of time the drive [Torque Current] is
below [Load Loss Level], before the action set in [Load
Loss Detect] is taken.

Parameter Number

292

Parameter Type

Read and Write

Display Units / Units

1 Second / Seconds

Factory Default

0 Sec

Minimum Value

0 Sec

Maximum Value

30 Sec

[Bus Reg Level]

– Firmware 4.001 & later

[Max Bus Volts]

When this parameter is set to the minimum value, the
drive DC bus voltage is limited to 110% of nominal voltage.
[Bus Limit En] must be “Enabled” for the drive to limit the
bus voltage. This setting is used to move the trigger point
for regulation above the turn-on point for dynamic brake
or regeneration packages.

Parameter Number

325

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

358/716/895 Volts

Minimum Value

358/716/895 Volts

Maximum Value

403/807/1009 Volts