Start-Up

5–5

Advanced Start-Up

This procedure is designed for complex applications requiring a
more detailed start-up.

Advanced Start-Up Procedure

Press these keys . . .

while following these steps . . .

The HIM Display will show . . .

Disconnect Motor

1. Remove the drive cover and disconnect the motor leads from TB1, terminals

U, V, W (T1, T2 and T3).

Apply Power

2. Apply AC power and control voltages to the drive. The LCD Display should

light and display a drive status of “Stopped” and an output frequency of “+0.00
Hz.”

If the drive detects a fault, a brief statement relating to the fault will be shown
on the display. Record this information, remove all power and correct the fault
source before proceeding. Refer to Chapter 7 for fault descriptions.

Stopped

+0.00 Hz

Reset Factory Defaults

3. Important: The remaining steps in this procedure are based on factory default

parameter settings. If the drive has been previously operated, parameter
settings may have been changed and may not be compatible with this start-up
procedure or application. Drive status and fault conditions may be unpredict-
able when power is first applied.

To obtain proper results, the parameters must be restored to factory default
settings.

A. From the Status Display, press Enter (or any key). “Choose Mode” will be

displayed.

B. Press the Increment (or Decrement) key until “EEPROM” is displayed. If

EEProm is not in the menu, programming is password protected. Refer to
Chapter 3 for Password information.

C. Press Enter.

D. Press the Increment (or Decrement) key until “Reset Defaults” is displayed.

E. Press Enter to restore all parameters to their original factory settings.

F.

Press ESC. “Reprogram Fault” will display, indicating successful reset.

G. Press the Stop key to reset the fault. Cycle power.

Choose Mode

Display

Choose Mode

EEProm

EEProm

Reset Defaults

Choose Mode

EEProm

Reprogram Fault

F48

Stopped

+0.00 Hz

or

or