Installation/Wiring

2–9

Input Devices

Starting and Stopping the Motor

Repeated Application/Removal of Input Power

Bypass Contactors

Electrical Interference - EMI/RFI

Immunity

The immunity of 1336

PLUS

II

drives to externally generated interfer-

ence is good. Usually, no special precautions are required beyond the
installation practices provided in this publication.

It is recommended that the coils of DC energized contactors associ-
ated with drives be suppressed with a diode or similar device, since
they can generate severe electrical transients.

!

ATTENTION: The drive start/stop control circuitry in-
cludes solid-state components. If hazards due to accidental
contact with moving machinery or unintentional flow of
liquid, gas or solids exist, an additional hardwired stop cir-
cuit may be required to remove AC line power to the drive.
When AC power is removed, there will be a loss of inherent
regenerative braking effect & the motor will coast to a stop.
An auxiliary braking method may be required.

!

ATTENTION: The drive is intended to be controlled by
control input signals that will start and stop the motor. A
device that routinely disconnects then reapplies line power
to the drive for the purpose of starting and stopping the
motor is not recommended.

!

ATTENTION: An incorrectly applied or installed bypass
system can result in component damage or reduction in
product life. The most common causes are:

• Wiring AC line to drive output or control terminals.

• Improper bypass or output circuits not approved by

Allen-Bradley.

• Output circuits which do not connect directly to the

motor.

Contact Allen-Bradley for assistance with application or
wiring.