Electrical configuration, Rfi filter installation, Rfi filter leakage current – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 199

Advertising
background image

CE Conformity

C–3

EMC Enclosure Kit Selection

RFI Filter Installation

Important: Refer to the instructions supplied with the filter for details.

The RFI filter must be connected between the incoming AC supply
line and the drive input terminals.

RFI Filter Leakage Current

The RFI filter may cause ground leakage currents. Therefore a solid
ground connection must be provided as shown below.

Electrical Configuration

Frame Reference

Enclosure Kit Catalog Number

200-240V Rating

380-480V Rating

500-600V Rating

A1, A2, A3

1336F-AE3

1336F-AE3

A4

1336F-AE2

1336F-AE2

1336F-AE2

B

1336F-AE4

1336F-AE4

1336F-AE4

C

1336F-AE5

1336F-AE5

1336F-AE5

D

1336F-AE6

1336F-AE6

1336F-AE6

E

1336F-AE7

1336F-AE7

1336F-AE7

!

ATTENTION: To guard against possible equipment
damage, RFI filters can only be used with AC supplies that
are nominally balanced and grounded with respect to
ground. In some installations, three-phase supplies are
occasionally connected in a 3-wire configuration with one
phase grounded (Grounded Delta). The filter must not be
used in Grounded Delta supplies.

JOG

ESC

SEL

R (L1)

S (L2)

T (L3)

L1

Line

L2

L3

E

L1'

Load

L2'

L3'

E'

PE

Conduit/4-Wire Cable

RFI Filter

Shield Terminated in Cable

Clamp on A Frame Drives

Nearest
Building Structure Steel