Adaptive i lim, Current limit en, Overload mode – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 92: Setup, Overload patterns

Advertising
background image

6–10

Programming

Setup

[Adaptive I Lim]

When ENABLED, this parameter maintains normal current
limit control to provide normal acceleration into medium to
high system inertia.

When DISABLED, this parameter applies a feed forward
command to acceleration, allowing quicker accel times
from stopped to commanded speed with low system
inertia

.

Parameter Number

227

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Current Limit En]

Enables or disables the software current limiting function
(does not disable voltage limiting).

Parameter Number

303

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Overload Mode]

This parameter selects the derating factor for the I

2

T elec-

tronic overload function. Motors designed to operate with wider
speed ranges need less overload derating.

Parameter Number

37

Parameter Type

Read and Write

Factory Default

“No Derate”

Units

Display Drive

“Max Derate” 2

2:1 Speed Range Derate below 50%
of Base Speed

“Min Derate” 1

4:1 Speed Range. Derate below 25%
of Base Speed

“No Derate” 0

10:1 Speed Range. No Derating

Min Derate

0

80

100

60

40

20

% of Load

% of Load

% of Load

No Derate

0

80

100

60

40

20

% of Base Speed

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

Overload Patterns

1

10

1

10

100

1000

Time to Trip vs. Current

Multiple of [Overload Amps]

Time to

Trip - Seconds

115%

Cold

Hot