Figure w figure x figure y figure ab, Figure ab, Figure z figure ab – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 163: Figure aa figure ab, Figure ae, Figure ad, Altitude and high input voltage, Figure/rating derate

Advertising
background image

Specifications and Supplemental Information

A–7

Figure W

C200

Figure X

C250

Figure Y

CX300

Figure Z

CP350
CPR350

Figure AA

CP400
CPR400

Figure AB

C300-C600

Enclosed drive in
40

° C. ambient

Figure AC

C300-C600

Enclosed drive in
41-50

° C. ambient

Figure/Rating Derate

Figure/Rating Derate

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

% of Drive

Rated Amps

Carrier Frequency in kHz

2

4

6

60%

90%

70%

50%

80%

100%

% of Drive

Rated Amps

Carrier Frequency in kHz

2

4

6

60%

90%

70%

50%

80%

100%

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Assumes two (2) 725 CFM cooling fans for

IP 20 (NEMA Type 1) enclosure

C350

C300

C400
C450
C500
C600

Carrier Frequency in kHz

2

3

4

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Assumes two (2) 725 CFM cooling fans for

IP 20 (NEMA Type 1) enclosure

C300/

C350
C400

C450

C500

C600

6kHZ Data Not Available at Time of Printing

Altitude and High Input Voltage

Figure/Rating Derate

Figure AD

Altitude - All
Ratings

Figure AE

High Input
Voltage

% of Drive

Rated Amps

Altitude

m

(ft)

100%

80%

90%

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

% of Drive

Rated Amps

Input Voltage

100%

80%

90%

240, 480 or 600V Nominal

+6%

+4%

+2%

+10%

+8%

Required Only for the following drives:

1336F-x025 – 18.5 kW (25 HP) at 8 kHz

1336F-x030 – 22 kW (30 HP) at 6 or 8 kHz
1336F-x060 – 45 kW (60 HP) at 6 kHz

Standard Rating for Enclosed Drive in
40

°C Ambient & Open Drive in 50°C Ambient.

Derating Factor for Enclosed Drive in
Ambient between 41

°C & 50°C.