Appendix

A

Specifications and
Supplemental Information

Specifications

Protection

200-240V Drive

380-480V Drive

500-600V Drive

AC Input Overvoltage Trip:

285V AC

570V AC

690V AC

AC Input Undervoltage Trip:

138V AC

280V AC

343V AC

Bus Overvoltage Trip:

405V DC

810V DC

1013V DC

Bus Undervoltage Trip:

200V DC

400V DC

498V DC

Nominal Bus Voltage:

324V DC

648V DC

810V DC

Heat Sink Thermistor:

Monitored by microprocessor overtemp trip.

Drive Overcurrent Trip

Software Current Limit:

20 to 160% of VT rated current.

Hardware Current Limit:

180 to 250% of VT rated current (dependent on drive rating).

Instantaneous Current Limit: 220 to 300% of VT rated current (dependent on drive rating).

Line transients:

up to 6000 volts peak per IEEE C62.41-1991.

Control Logic Noise Immunity: Showering arc transients up to 1500 volts peak

2

.

Power Ride-Thru:

15 milliseconds at full load.

Logic Control Ride-Thru:

0.5 seconds minimum, 2 seconds typical.

Ground Fault Trip:

Phase-to-ground on drive output.

Short Circuit Trip:

Phase-to-phase on drive output.

Environment

Altitude:

1000 m (3300 ft) max. without derating.

Ambient Operating Temperature

IP00, Open:

0 to 50 degrees C (32 to 122 degrees F).

IP20, NEMA Type 1 Enclosed:

0 to 40 degrees C (32 to 104 degrees F).

IP54, NEMA Type 12 Enclosed:

0 to 40 degrees C (32 to 104 degrees F).

IP65, NEMA Type 4 Enclosed:

0 to 40 degrees C (32 to 104 degrees F).

Storage Temperature (all constructions):

–40 to 70 degrees C (–40 to 158 degrees F).

Atmosphere

Important: Drive must not be installed in an area where
the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the drive is not going to be installed
for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.

Relative Humidity:

5 to 95% non-condensing.

Shock:

15G peak for 11ms duration (

±1.0ms).

Vibration:

0.006 inches (0.152 mm) displacement, 1G peak.

Agency Certification:

1

Note: Installation guidelines called out in Appendix C must be adhered to.

2

Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high
[Pulse Freq] readings.

U.L. Listed
CSA Certified

Marked for all applicable directives

1

Emissions

EN 50081-1
EN 50081-2
EN 55011 Class A
EN 55011 Class B
EN 61800-3

Immunity

EN 50082-1
EN 50082-2
IEC 801-1, 2, 3, 4, 6, 8 per EN 50082-1, 2
EN 61800-3

Low Voltage

EN 60204-1
PREN 50178

Q