Process display, Process 1 par, Process 1 scale – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 131: Process 1 txt 1-8, Process 2 par, Process 2 scale, Process 2 txt 1-8

Advertising
background image

Programming

6–49

Process

Display

This group of parameters contains the parameters used to scale, in “User Units”, any drive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.

[Process 1 Par]

This parameter should be set to the number of the param-
eter whose scaled value will be displayed on Line 1 of the
HIM Display Panel.

The maximum process value that can be displayed is
99,999.99. If this value is exceeded, a character string of
asterisks (****) will appear on the display.

Parameter Number

127

Parameter Type

Read and Write

Display Units / Drive Units

Parameter # / Parameter #

Factory Default

1

[Process 1 Scale]

This value sets the scaling multiplier for [Process 1 Par].
The displayed value will be:

Parameter Number

128

Parameter Type

Read and Write

Display Units / Drive Units

Numeric / Scale x 100

Factory Default

+1.00

Minimum Value

–327.68

Maximum Value

+327.67

[Process 1 Txt 1-8]

Sets the “User Units” description for the value determined
by [Process 1 Par] and [Process 1 Scale]. This 8 character
description will be shown on line 1 of the display. Refer to
the Character Map in Appendix A.

Parameter Number(s)

129-136

Parameter Type

Read and Write

Display Units / Drive Units

ASCII Code / ASCII Code

Factory Default

“Volts ”

[Process 2 Par]

This parameter should be set to the number of the param-
eter whose scaled value will be displayed on Line 2 of the
HIM Display Panel.

The maximum process value that can be displayed is
99,999.99. If this value is exceeded, a character string of
asterisks (****) will appear on the display.

Parameter Number

180

Parameter Type

Read and Write

Display Units / Drive Units

Parameter # / Parameter #

Factory Default

54

[Process 2 Scale]

This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:

Parameter Number

181

Parameter Type

Read and Write

Display Units / Drive Units

Numeric / Scale x 100

Factory Default

+1.00

Minimum Value

–327.68

Maximum Value

+327.67

[Process 2 Txt 1-8]

Sets the “User Units” description for the value determined
by [Process 2 Par] and [Process 2 Scale]. This 8 character
description will be shown on line 2 of the display. Refer to
the Character Map in Appendix A.

Parameter Number(s)

182-189

Parameter Type

Read and Write

Display Units / Drive Units

ASCII Code / ASCII Code

Factory Default

“Amps ”

[Process 1 Par] actual value

x [Process 1 Scale] value

Displayed Value

[Process 2 Par] actual value

x [Process 2 Scale] value

Displayed Value