6–64

Programming

The following parameter appears only in the Linear List and is not
documented elsewhere.

Step Logic

[SL0 Time]

– Firmware 5.001 & later

[SL1 Time]
[SL2 Time]
[SL3 Time]
[SL4 Time]
[SL5 Time]
[SL6 Time]

Sets the time to remain in each step if the corresponding
Logic Step or Jump is set to “Step On Time”. To use the
encoder or pulse counts this must be set to “0.00.”

Parameter Number 339, 345, 351, 357, 363, 369, 375
Parameter Type

Read and Write

Display Units / Units

0.01 Second / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

600.00 Sec

[SL0 Encoder Cnts]

– Firmware 5.001 & later

[SL1 Encoder Cnts]
[SL2 Encoder Cnts]
[SL3 Encoder Cnts]
[SL4 Encoder Cnts]
[SL5 Encoder Cnts]
[SL6 Encoder Cnts]

Sets the number of encoder or pulse counts necessary to
cause a step if the corresponding Logic Step or Jump is
set to “Step On Time.” Current counts are stored when a
step is initiated. The difference between the current and
stored counts is compared to the parameter. The encoder
counts are directional and stop at the Min and Max values.
A F69 Step Logic fault will occur when using the encoder
and [Encoder Counts] is at an end point. The pulse counts
are only positive and will rollover internally.

To use the encoder counts, set the Logic Step or Jump to
“Step on Time,” “Time and SLx” or “Time not SLx.” The
[SLx Time] must be set to “0.00.” Set the [SLx Step Setting]
“Encoder/Puls” to “0.” To use pulse counts, connect an LA5
card to the drive. Set the [SLx Step Setting] “Encoder/Puls”
to “1.”

Parameter Number 340, 346, 352, 358, 364, 370, 376
Parameter Type

Read and Write

Display Units / Drive Units

1 Count / Counts

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

[Current Step]

– Firmware 5.001 & later

This parameter displays the current step the Step Logic
function is using. For example if [Current Step] is 2, the
SL2 parameters are active. This parameter can be used
to force the drive to a giving step.

Parameter Number

377

Parameter Type

Read and Write

Display Units /Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

9

Linear

List

This group lists all the parameters currently installed in your drive in numerical order. Refer
to the Appendix at the back of this manual for an alpha/numeric listing of all parameters.

[Bidir In Offset]

Trims the offset of the bi-directional inputs on LA6 & LA7
option cards. To provide an equal response to positive and
negative signals, this parameter may need to be adjusted
for each board. With no voltage on input 0, monitor [Anlg
In 0 Freq] and adjust [Bidir In Offset] until it is zero.

Parameter Number

329

Parameter Type

Read and Write

Display Units / Drive Units

None

Factory Default

270

Minimum Value

0

Maximum Value

1024