ADS Environmental Services FlowShark QR 775003 A2 User Manual

Page 211

Advertising
background image

8-26

ADS FlowShark IS Manual

Problem

Raw ultrasonic depth data shows depths greater than
the pipe diameter.

Possible

Causes

Physical offset may be incorrect.

Pipe height may be incorrect.

Pipe may be surcharged.

Sensor may be dirty.

Sensor may be faulty.

Possible

Solutions

Verify the physical offset.

Verify the pipe height.

Clean the sensor.

Replace the sensor.

Contact your regional ADS representative.

Problem

Ultrasonic depth data indicates a surcharged pipe, but
the pipe is free flowing.

Possible

Causes

Physical offset may be incorrect.

Pipe height may be incorrect.

Sensor may be dirty.

Sensor may be faulty.

Analog board may be faulty.

Possible

Solutions

Verify the physical offset.

Verify the pipe height.

Clean the ultrasonic depth sensor.

Contact your regional ADS representative.

Replace the sensor.

Replace the monitor if defective.