IDK MSD-54 Series Command Guide User Manual

Page 93

Advertising
background image

MSD-54 Series Users Guide (Command Guide)

93

@SEC

Set control command (Display received data)

Command
format

@SEC, no, delay, port, memo, length, command, timeout, retry, interval, retryover,
display

, delimiter

Return value
format

@SEC, no, delay, port, memo, length, command, timeout, retry, interval, retryover,
display

, delimiter

Parameter

no

: Command number

1 to 32

delay

:

0 to 999999

port

: Output port

1 to 2047

bit10

bit9

bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1

bit0

Outp
ut
port

LOOP
BACK

LAN8

LAN
7

LAN
6

LAN
5

LAN
4

LAN
3

LAN
2

LAN
1

RS-232
C CH2

RS-232
C CH1

Specify “1” for the bit of the output port from which the command is sent (Since bit
15-11 are not used, always specify “0”). For example, if you send a command to
RS-232C CH1, specify “1”(0000000000000001 in binary). If sending a command to
LAN 1 and LAN 2, specify “12”(0000000000001100 in binary).

memo

:

Up to 14 characters of 20 to 7D except 2C (,). “2 ASCII codes”

length : Data size of the sent command (the number of bytes)

0 to 30

command : Send command data

Specify length × 2 digits with 0 to 9, A to F, a to f = 4 bit per digit (in

hexadecimal)

timeout

:

0 to 99999

retry

:

0 to 99

interval

: Interval between retries

0 to 99999

retryover

: Processing at retry timeout

0 = Stop processing, 1 = Continue processing

display :

Displaying received data

1 = In ASCII codes, 2 = In hexadecimals

delimiter

:

Specify 2 digits of 0 to 9, A to F, a to f = 4 bit per digit (in hexadecimal) in order
to monitor delimiters

100 = Not monitor