IAI America RCS3PCR-SS8C User Manual
Page 75
Advertising
7. Setting the Home
65
(3) Click the parameter button.
(4) Select “Axis-specific Parameters.”
(5) When the axis-specific parameter screen opens, select No. 12, “Home preset.”
(6) Change the setting of Axis-specific Parameter No. 12 (home preset).
Add or subtract the value measured in (2) to/from the value currently entered.
The setting unit is 0.001 mm.
Example: If the difference is “-1 mm”:
Home preset = Current setting – 1000
(7) Write the new data.
Click this button to open the parameter edit
screen.
Select “Axis-specific Parameters.”
Select No. 12, “Home preset.”
Click the SEL button to write the new
data to the controller.