Alarm, Input filter and moving average, Display zone – Yokogawa DAQWORX User Manual

Page 102: Alarm -6, Input filter and moving average -6, Tag -6, Display zone -6, Input flter and movng average, Dsplay zone

Advertising
background image

5-6

IM WX104-01E

Alarm

Four alarms (Alarm 1 to 4) can be specified on each channel.

Type

Select H, L, h, l, R, T or t. T or t is selectable when the style number is greater than or

equal to 2. The selectable alarms vary depending on the input mode and computation

type. For details, see section 6.2 in the User's Manual IM04L02A01-01E.

Alarm value

Alarm is generated using the specified value as the boundary. The selectable range of

alarm values vary depending on the input mode and range.

Alarm delay

Alarm is generated when the measured value stays above or below the specified alarm

value for the specified time (delay period).

Relay

To output relays, select the output relay number. Otherwise, select [NONE].

Input Flter and Movng Average

Moving average can be specified on models DX106, DX112, DX210, DX220, DX230,

MV106, MV112, MV210, MV220, and MV230.

Input filter can be specified on models DX102, DX104, DX204, DX208, MV102, MV104,

MV204, and MV208.

Input flter

To use the input filter, select the time constant (2 s, 5 s, or 10 s).

Movng average

To use the moving average, select the sampling count (2 to 16).

Tag

Up to 16 characters can be entered for the tag.

You can use the tag name instead of the channel name to be displayed on the screen.

The [Setup] screen is used to select whether to display the channel name or the tag

name on the screen.

If tag is selected in the [Setup] screen, you will be able to select tag No., tag comment, or

tag in the Data Monitor or Data Viewer.

Dsplay Zone

You can select the range of the screen in which the waveform of each channel is to be

displayed.

Specify positions (%) on the display scale for the upper and lower limits.

The conditions for setting the zones are as follows:

• Range: 0% to 100%

The lower limit must be less than the upper limit

• The difference between the lower and upper limits is at least 5%.

5.2 Settng the Measurement Channels

Advertising