Event date, Event date -30 – Yokogawa DAQWORX User Manual

Page 226

Advertising
background image

7-30

IM WX104-01E

Event Date

Event related settings are enabled when [Data Kind] is set to [E+D] or [Event] in [Basic

Environment] under [Environment] in the [Basic Setting] tab.

Sample rate

Select the data recording interval from the available settings. You cannot specify a

sampling rate that is faster than the scan interval.

Mode

Settngs

Descrpton

Free

Records data continuously.

Single

Records data when the trigger condition is met.

Repeat

Records data each time the trigger condition is met.

Data length

Select the size of a record data file. The recorded data is divided by the file size

specified here. The available data lengths vary depending on the Sample rate setting.

Sample rate

Selectable range

of data length

Sample rate

Selectable range

of data length

Sample rate

Selectable range

of data length
* Selectable on the MV1004, MV1008 and MV2008

25 ms*

25 ms

250 ms

500 ms

1 s

10 min to

10 min to

10 min to

10 min to

10 min to

4 hours

1 day

2 days

3 days

7 days

2 s

5 s

10 s

30 s

1 min

10 min to

10 min to

10 min to

1 hour to

1 hour to

14 days

31 days

31 days

31 days

31 days

2 min

5 min

10 min

1 hour to

1 hour to

1 hour to

31 days

31 days

31 days

Pre-Trgger

Specify the range when recording data before the trigger condition is met. Select the

range as a percentage of the data length from 0, 5, 25, 50, 75, 95, and 100%. If you do

not want to record the data existing before the trigger condition is met, select 0%.

Trgger Sgnal Key

Select [ON] if you want to activate the trigger using key operation.

7.4 Enterng General Settngs