Yokogawa DAQWORX User Manual

Page 289

Advertising
background image

8-32

IM WX104-01E

Start target setpont

Set the start SP, a starting condition, in the range of [EU (0.0% to 100.0%)] (initial value

is 0%) of the measurement span. Only the loops that are set as follows are displayed:

[Setup] tab > [Internal Loop] > [Program control] to [On] During cascade control, even-

numbered loops within the same terminal block are not displayed.

Start code

Select the operation start condition from the following. However, only the possible loop

conditions are displayed.

Starting target setpoint start, PV1 to PV 6 ramp-prioritized PV start, time-prioritized ramp

start (not displayed for segment time ramp setting method)

Wat acton settng

Set the wait zones for 6 (number of loops) × 5 (number of zones) (2 (number of loops)

× 5 (number of zones) for the CX1000) in the range of “EUS (0.0 to 100.0%)” of the

measurement span.

On Style 3 or later, the value can be set on the loop whose Action Loop Set is ON. On

Style 2 or earlier, the value can be set on loops whose [Program Control] has been

turned ON in [Internal Loop] under the [Setup] tab. During cascade control, even-

numbered loops within the same terminal block cannot be set.

Wat tme

Set the wait time in [hh:mm:ss] format (selectable range: [00:00:00] to [99:59:59]) for all

the available zones. This item applies to all zones. You cannot set this value when the

wait zone is OFF on all loops.

Acton Loop Set

Set the loops to activate.

Select from the loops whose program control is ON.

8.6 Program Control Related Setup Operatons