Index – Yokogawa DAQWORX User Manual

Page 264

Advertising
background image

8-7

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the CX1000/CX2000

• AUX

Remote Setting

When performing measurements by remote, select [Remote]. When [Control Mode]

is set to [Cascade], it is not possible to set [Remote] for secondary measurement loop

numbers. Selection is not possible for the following:

• Secondary measurement loop numbers when [Control Mode] is set to [Cascade].

• Even-numbered loops when the number of loops is 2, 4, or 6 (6/4LOOP Select is

set to 4) and [Control Mode] is set to [PVSwitch] (when PV/SP math function is

OFF).

• When the number of loops is 6 (6/4LOOP Select is set to 6) and [Control Mode] is

set to [PVSwitch] (when PV/SP math function is OFF).

Alarm Mode

Select from the following whether you want the alarm to be inactive.

ALWAYS:

Alarm is always active.

STOP:

Alarm inactive when operation is stopped.

STOP/MAN:

Alarm is inactive in manual operation mode or when operation is stopped.

• Output Process

When [Control Mode] is set to [Cascade], the output process settings are not

available.

Control Output

Select the type of control output from the following:

• Relay

• Voltage-pulse

• Current-output

• On/Off-control relay contact output (not selectable for retransmission loops)

Cycle Time

With a PID proportional to time, set the cycle time (control output cycle) between [1]s

and [1000]s.

Analog-output Type

For the current output, select the output current range from the following:

• [4-20mA], [0-20mA], [20-4mA], and [20-0mA].

8.3 Control Functon Basc Settngs