Select the loops numbers, measurement channel numbers, or DIO numbers (Style 3

or later) you want to assign to a Group. For the CX1000, you can select 1 or 2 internal

loops and 1 to 4 external loops. For the CX2000, you can select 1 to 6 internal loops, 1

to 16 external loops, and 1 to 36 DIOs.

Group1 consists of up to 4 types on the CX1000, or up to 6 types on the CX2000

corresponding to the control loops and measurement channels.

DIO Montor (CX Style Number S3 or Later)

Entry Num

Set the value in the range from 1 to 36.

Use

Turns ON/OFF the specified DIO entry number.

DIO Knd

Set the method of DIO monitor.

DI-1:

Indicates the DI input status. The internal switch status is not output.

DO-1:

Outputs the internal switch status using a single DO. If the internal switch is

ON, 1 (ON) is output. If it is OFF, 0 (OFF) is output.

DO-2:

Outputs the internal switch ON/OFF status using separate DOs. If the internal

switch is ON, 1 (ON) is output from the ON output DO. If it is OFF, 0 (OFF) is

output from the OFF output DO. If the internal switch is OFF, 1 (ON) is output

from the ON output DO. If it is OFF, 0 (OFF) is output from the OFF output DO.

DIO-11:

Displays the input status of the specified DI as well as operates in the same

fashion as D0-1.

DIO-12:

Displays the input status of the specified DI as well as operates in the same

fashion as D0-2.

DO-2P:

Outputs the internal switch ON/OFF status using separate DOs. If the internal

switch is ON, a pulse signal of 1- to 2-second pulse width is output from the

ON output DO. If it is OFF, a pulse signal of 1- to 2-second pulse width is

output from the OFF output DO.

DOI-12P: Displays the input status of the specified DI as well as operates in the same

fashion as D0-2P.

SW Num

Set the internal switch number to be assigned to the DO.

DO Num

Set the DO that is to perform DIO monitor. If the DIO Kind is set to DO-2, DIO12, DO2P,

or DIO-12P, set a separate DO for ON and OFF. The DO numbers cannot overlap

including those of other DIO entry numbers.

This does not appear when DIO Kind is DI-1.