Report, Report -39, Index – Yokogawa DAQWORX User Manual

Page 235

Advertising
background image

7-39

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the MV1000/MV2000

Report

Click to display the channel selection screen.

Channel selection screen

Click the channel you wish to set up

Report knd

Select the type of report to be created.

Settngs

Descrpton

OFF

Do not create a report.

Hour

Creates hourly reports.

Day

Creates daily reports.

Hour+Day

Creates hourly and daily reports.

Day+Week

Creates daily and weekly reports.

Day+Month

Creates daily and monthly reports.

Day, Week day, and Tme (hour)

Set the date or day of the week and the time when the report is to be created. The

specified date/time is when the report file is divided. Set the values in the range

indicated below. Items with a dash are invalid.

Report Type

Day

Week day

Tme

Hour

-

-

0 to 23

Day

1 to 28*

-

0 to 23

Hour+Day

-

-

0 to 23

Day+Week

-

SUN to SAT

0 to 23

Day+Month

1 to 28*

-

0 to 23

* You cannot specify 29, 30, or 31.

Report Channel No.

The report is output in order by this number.

Use

Select [ON] for the report channels to be used.

CH No.

Set the channel to assign to the report channel. All channels can be assigned, but

reports are not created for channels set to [Skip] or [OFF] even if they are assigned.

Sum Scale

Set the sum scale to [/s] to [/day] to match the unit of the measured value.

Example: If the unit of the measured value is “m

3

/min,” select [/min].

OFF Sums as-is the measured data per scan interval.

7.5 Enterng Basc Settngs

Advertising