Index

Conf

gur

ng the DX1000/DX2000

Command settng
• Clent command No.

Select from 1 to 16 for the transmitted command numbers to be configured.

• Command

Set the command type.

Settngs

Descrpton

Read

Read to the external input channel (16-bit signed integer type) from the server.

R-Math

Read to the communication input data (32-bit floating point type) from the
server.

Write

Write the measurement channel (16-bit signed integer type) to the server.

W-Math

Write the measurement channel (32-bit signed integer type) to the server.

Exchange-M Read to the communication input data (32-bit floating point type) from the

server/write the custom display value to the server (release numbers 4 and
later).

[Read] can be selected on DX2000s with the external input channel (/MC1 option) installed.

[R-Math], [W-Mat], and [Exchange-M ] can be selected on models with the computation

function (/M1 or /PM1 option) installed.

• Start channel/End channel (clent channels)

Enter the first and last channel numbers of input/output. The range of channels that

you can enter varies depending on the command type as follows:

Read: 201 to 440, R-Math: C01 to C60, Write: 1 to 48, W-Math: 101 to 160

Exchange-M (release numbers 4 and later): C01 to C60

• Connected to (server number)

Select the server number from 1 to 16.

• Regster

Set the register number of the server.

For an input register, select in the range of 30001 to 39999 and 300001 to 365536.

For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.

The register numbers you can specify vary depending on the command type. See

section 6/3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual

(IM04L41B01-17E).

• Type

Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or

FLOAT_L.

The register numbers you can specify vary depending on the command type. See

section 6.3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual

(IM04L41B01-17E).

In release number 3, FLOAT has been added as a data type for measurement channel

data and computation channel data.

6.5 Enterng Basc Settngs