Index – Yokogawa DAQWORX User Manual

Page 162

Advertising
background image

6-35

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the DX1000/DX2000

• Date format

Settngs

Dsplay Example

Y/M/D

2005/11/30

M/D/Y

11/30/2005

D/M/Y

30/11/2005

D.M.Y

30.11.2005

Appled Range

The format is applied to the date displayed on the screen. It does not change the

date format on the setup screen of the date/time, the date in the output data via
communications, the date saved along with the data, and the date used in the data file
names.

• 1st weekday (Release number 3 or later)

This setting specifies how to display the calendar that you use to search past

measured data. You can set the first day of the week to Sunday or Monday.

• Servce port

The following table indicates the number of simultaneous uses (number of users that

can use the function simultaneously), the maximum number of connections, and the

port number for each function.

Functon

Maxmum Number
of Connectons

Number of
Smultaneous Uses
Admnstrator User

Port Number

FTP server

2

2

2

*1

21/tcp

*3

Web server

80/tcp

*3

SNTP server

123/udp

*3

Modbus server

2

502/tcp

*3

Instrument information server

34264/udp

*2

*1 There are user limitations. For details, see the DX1000/DX1000N/DX2000 Communication

interface User’s Manual (IM04L41B01-01E).

*2 The port number is fixed.

*3 The default port number. You can set the value in the range of 1 to 65535. Use the default

port number unless there is a special reason not to do so.

• Status Relay

In the [System Configuration] screen, if [FAIL] is set to [FAIL/Alarm relay] (/F2 option)

or [FAIL/Status relay] (/F1 option), the [Status Relay] setting items are displayed.

Fal Relay, Status Relay (Release numbers 4 and later)

For this function, there are relays labeled “FAIL” and “Status” on the rear panel. You

can assign operations to these two relays. On a relay that has been set to “Status

relay,” you must also set the DX status that will be relayed (see below).

Memory/Meda Informaton, Measurement Error, Communcaton Error,
Memory Stop, Alarm

The relay contact output is turned on when an item that is set to [ON] occurs. [Alarm]

is available in release numbers 3 and later.

6.5 Enterng Basc Settngs