Index

Conf

gur

ng the CX1000/CX2000

• Bias (PV1/2 or Remote)

Turns ON/OFF the use of the bias.

When it is ON, set the value in the EUS (–100 to 100%) range of the measurement.

• Filter (PV1/2 or Remote)
Turns ON/OFF the use of the filter.

When it is ON, set the value between 1 and 120 s.

[Lnearzer] Tab

• Mode

Set the mode to [OFF], [Biasing], or [Approximation].

• Input

Set the linearizer input value. (The value varies depending on the mode.)

Biasing:

Set the value in EU (–5.0 to 105.0%) of the measurement span.

Approximation: Set the value in EU (–5.0 to 105.0%) of the measurement span.

You must set between 2 and 11 points total.

• Output

Set the linearizer output value. (The value varies depending on the mode.)

Biasing:

Set the value in EUS (–100.0 to 100.0) of the measurement span.

Approximation: Set the value in EU (–5.0 to 105.0%) of the measurement span.

Note

• For biasing, set the values so that input + output is EU (0 to 100%). In addition, set the

values so that input + output is greater than or equal to the previous input + output.

• Set the approximation output to be greater than or equal to the previous value.

• If a value smaller than the previous value is specified for the third point or later, the settings

after that point are invalid.

• When PV/SP math function is OFF, enter the settings above for each control loop in the

[Control Loop] tab. For the setting procedure, see page 6-22.

8.4 Control Functon General Settngs