Index – Yokogawa DAQWORX User Manual

Page 146

Advertising
background image

6-19

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the DX1000/DX2000

Trend nterval [/dv]

Select the time corresponding to 1 division of the time axis on the trend display from

below: You cannot specify a trend interval that is faster than the scan interval. See the

table under “Save Interval” below.

15s*, 30s, 1min, 2min, 5min, 10min, 15min, 20min, 30min, 1h, 2h, 4h, and 10h

* Can be set on the DX1002, DX1002N, DX1004, DX1004N, DX2004 and DX2008.

Save Interval (when recordng dsplay data)

Select the size of a record data file. The recorded data is divided by the file size

specified here. The available settings vary depending on the Trend interval setting.

Trend interval

Selectable range of

auto save interval

Trend interval

Selectable range of

auto save interval

Trend interval

Selectable range of

auto save interval

*1 Selectable on the DX1002, DX1002N, DX1004, DX1004N, DX2004, and DX2008 (release

number 3 or later).

*2 Selectable in fast sampling mode on the DX1006, DX1006N, DX1012, DX1012N, DX2010,

DX2020, DX2030, DX2040, and DX2048 (release number 3 or later).

5 s*

1

10 s*

1

15 s*

2

30 s

1 min

10 min to

10 min to

10 min to

10 min to

10 min to

12 hours

1 day

3 days

7 days

14 days

2 min

5 min

10 min

15 min

20 min

10 min to

10 min to

10 min to

10 min to

1 hour to

14 days

31 days

31 days

31 days

31 days

30 min

1 h

2 h

4 h

10 h

1 hour to

1 hour to

2 hours to

4 hours to 8 hours to

31 days

31 days

31 days

31 days

31 days

Crcular Tme Per revoluton [/rev]

Select the time of revolution from [20min]* to [4week].

* For release number 2 or earlier, this can only be specified on the DX2004 and DX2008.

For release number 3 and later, this can be specified during the fast sampling mode on the

DX2010, DX2020, DX2030, DX2040 and DX2048 in addition to DX2004 and DX2008.

Crcular Save Interval

Select the size of a record data file. The recorded data is divided by the file size

specified here. The available settings vary in the range of [10min] to [31day] depending

on the [Time Per revolution] setting.

Crcular Offset Tme

The time at the reference position on the circle can be offset in unit of an hour up to 23

hours. The available settings vary depending on the [Time Per revolution] setting.

Dsplay Update 2nd Interval

Enabled when [Trend Rate Switching] is turned [ON] under [Environment] - [Detail

Setting] in the [Basic Setting] tab. Select a rate from the list.

The selectable 2nd intervals are the same as those for Trend interval.

Drecton

Set the display direction of the trends to [Horizontal], [Vertical], [Wide], or [Split].

Trend Clear

Settngs

Descrpton

ON

Clears the displayed waveform when the memory sampling is started.

OFF

Does not clear the waveform when the memory sampling is started.

This is fixed at [ON] if you are using the multi batch function (/BT2 option; release

number 3 or later). You can set the multi batch function by setting [Batch operation qty]

under [Environment] - [Detail Setting] in the [Basic setting] tab.

6.4 Enterng General Settngs

Advertising