Conf

gur

ng the DX1000/DX2000

• Dgt of lot number

Select the number of digits of the lot number from 4, 6, or 8. Select [OFF] to disable

the lot number.

• Auto ncrement

ON Automatically sets the lot number of the next measurement to “the lot number of

the current measurement + 1.”

• Trend Type

Function for the DX2000 only.

Settngs

Descrpton

T-Y

A trend display with a linear time axis

Circular

A trend display with a circular time axis

• Partal

Turn Partial [ON] (partially expand) or [OFF] (do not partially expand).

• Trend Rate Swtchng

ON Enables the function that switches the trend interval while the memory sampling

is in progress. The “Second interval [/div]” item is displayed in the setting mode.

• When [Trend Rate Switching] is set to [ON], you cannot set [Data Kind] under

[Environment] - [Basic Environment] in the [Basic setting] tab to [E+D].

• This setting is fixed at [OFF] if you set [Batch operation qty] to [2] or higher on models

with the multi batch function (/BT2 option; release number 3 or later).

• Wrte Group

Settngs

Descrpton

Common

Write the message to all groups.

Separate

Write the message to the displayed group.

• Power-Fal Message

ON A message is written when the DX recovers from a power failure while memory

sampling is in progress.

• Change Message

ON Writes the time the interval is switched and the new trend interval as a message

when the trend interval is switched.

• Scale over

Settngs

Descrpton

Free

The value is set to –over range if the value is less than –30000 and +over
range if the value is greater than 30000 excluding the decimal point. The
value is displayed as –Over and +Over, respectively.

Over

The value is set to –over range if the value is less than –5% of the scale and
+over range if the value is greater than 105%. The value is displayed as –
Over and +Over, respectively.

Example:

If the scale is 0.0 to 200.0, the value is set to –over range if the value is less than

–10.0 of the scale and +over range if the value is greater than 210.0.

Note

For computations such as TLOG, CLOG, and report, the handling of the scale over-range value

can be set in advance.

• Alarm No Loggng

Turn ON when using the Alarm No Logging function. The [Detect] setting is enabled in

the Measure channel/Math channel/Ext channel tab(s).