Yokogawa DAQWORX User Manual

Page 181

Advertising
background image

6-54

IM WX104-01E

MODBUS Clent

Communcaton nterval

Set the read cycle to 125ms, 250ms, 500ms, 1s, 2s, 5s, or 10s.

Auto recovery

Set the interval for retrying the connection when the connection is interrupted for some

reason. Select OFF, 10s, 20s, 30s, 1min, 2min, 5min, 10min, 20min,30min, or 1h.

Modbus Server settng
• Server No.

Select from 1 to 16 for the server registration numbers to be configured.

• Port No.

Enter the port number in the range of 0 to 65535 for the selected server. The default

value is 502.

• Host Name

Set the destination Modbus server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name.

• You can also set the IP address. In this case, the DNS is not required.

• Unt

Select [Auto] if the unit number of the destination server is not required; Otherwise,

select [Fixed]. If you select [Fixed], the [Unit No.] item is displayed.

• Unt No.

Enter a fixed unit number in the range of 0 to 255.

6.5 Enterng Basc Settngs