Control relay, Control relay -11 – Yokogawa DAQWORX User Manual

Page 268

Advertising
background image

8-11

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the CX1000/CX2000

Control Relay

Module Settng

Select the terminal blocks where you want to register contact inputs from [CTRL1-2],

[CTRL3-4], [CTRL5-6], or [EXTDIO]. [CTRL3-4], [CTRL5-6], and [EXTDIO] are available

only for the CX2000.

FAIL

Activates the output of a relay contact signal (FAIL signal) if a fault occurs in the CX

CPU. When it is [ON] (default: [OFF]), contact output number [DO001] of control output

terminal block 1 is automatically assigned to [De_energize/Nonhold].

Self Dagnoss

Activates the output of a relay contact signal in the event of input burnout, an A/D

converter fault, or reference contact compensation failure. When it is [ON] (default:

[OFF]), contact output number [DO002] of control output terminal block 1 is automatically

assigned to [De_energize/Nonhold].

Relay (Acton/Behavor)

Set the contact output relay operating mode to [De_energize/Hold], [De_energize/

Nonhold], [Energize/Hold], or [Energize/Nonhold].

8.3 Control Functon Basc Settngs