Control Functon General Settngs

Make settings for the internal loop control functions, using the [Control Loop] tab and

[Control Group] on the [Setting] tab. You can also enter these settings by choosing [Control

Setting] - [SETUP [Regular] Setting] - [Control Loop], or [Control Settings] - [SETUP

[Regular] Setting] - [Control Group].

On the [Control Loop] tab, click the button (LOOP01, LOOP02, ...) of each loop number

that you want to set, and then make the settings for that loop. The label of the selected

loop number button is red. Select each item (Control Input, PID/Alarm, Operation

Related, Linearizer, and Control Function) with the option buttons.

Control Input

The menu that appears varies depending on whether the PV/SP math function in Control

Action is ON/OFF.

When the PV/SP Math Functon Is OFF

The control input types that appear vary depending on the [Internal Loop] > [Control

Mode] setting under the [Setup] tab. The input types that you can select are [PV1], [PV2],

[Remote], and [PVrange]. They are displayed under the following conditions.

PV1

PV1

Remote

PVrange

Basc

Odd loops
Even loops

Cascade

Odd loops
Even loops

PVSwtchng

Odd loops

*

Even loops

Retransmsson
(Style 3 or later)

Odd loops
Even loops

* With 6 loops, and 6/4LOOP Select set to 6 loops.

Remote appears if the Setup tab's Internal Loop > Remote setting is set to Remote.

The settings displayed depend on the input type, [PV 1], [PV2], [Remote], and [PVrange],

but the settings are the same.

Select the loop number

SCALE/1-5V (PV1, PV2, Remote)

Select the channel measurement mode from [Temp], [Scale], or [1-5V].