Input type (mode and range/type), Linear scaling (scale), Difference computation (delta) – Yokogawa DAQWORX User Manual

Page 132: Input type (mode and range/type) -5, Linear scaling (scale) -5, Difference computation (delta) -5, Index, Lnear scalng (scale), Dfference computaton (delta)

Advertising
background image

6-5

IM WX104-01E

1

2

3

4

5

6

7

8

9

Index

Conf

gur

ng the DX1000/DX2000

Input Type (Mode and Range/Type)

Correspondence between difference computation, scaling, and square root computation

([DELTA], [SCALE], and [SQRT]) is as follows.

Mode

OFF

DELTA

SCALE

SQRT

SKIP

Yes

No

No

No

VOLT (voltage)

Yes

Yes

Yes

Yes

TC (thermocouple)

Yes

Yes

Yes

No

RTD (resistance temperature detector)

Yes

Yes

Yes

No

DI (voltage level/contact input)

Yes

Yes

Yes

No

1-5 V

No

No

Yes

No

The values in the Range/Type list box vary depending on the above settings.

The following input types have been added in release number 3.

Mode

Input Type

Descrpton

TC

Type XK

XK GOST, /N3 option

RTD

Pt100G

Pt100GOST, /N3 option

Cu100G

Cu100GOST, /N3 option

Cu50G

Cu50GOST, /N3 option

Cu10G

Cu10GOST, /N3 option

Pt46G

Pt46GOST, /N3 option

The following input types have been added in release number 4.

Mode

Input Type

Descrpton

RTD

Pt200W

Pt200 (WEED), /N3 option

Span L, Span U

Input range. The selectable range is displayed on the screen. The selectable range for

Type N has been expanded (from –270.0 to 1300.0°C) in release number 3.

Note

• You cannot set the same value to [Span L] and [Span U].

• When the [Mode] is [1-5V] or [Sqrt], [Span L] must be less than [Span U].

Lnear Scalng (SCALE)

Converts the unit to obtain the measured value.

• Scale L, Scale U

Input range after converting the unit. The selectable range is from –30000 to 30000.

• Pont

Set the number of digits to the right the decimal to four digits or less (0 to 4).

Note

• The DX converts the measured value to a value obtained by removing the decimal point

from the value span specified by [Scale L] and [Scale U]. For example, if the scale setting is

“–5 to 5,” the value is converted to a value within the span of “10”; if the scale setting is “–5.0

to 5.0,” the value is converted to a value within a span of “100.” In this case, the resolution

of the value converted to a span of “10” is lower than the value converted to a span of “100.”

To prevent the display from becoming rough, it is recommended that the scale be set so that

this value is greater than 100.

• You cannot set the same value to [Scale L and [Scale U].

• When the [Mode] is [1-5V] or [Sqrt], [Scale L] must be less than [Scale U].

Dfference Computaton (DELTA)

Displays the difference between the input and the reference channel.

If difference computation is performed between channels that have different range and

type settings, the decimal position of the computed result is set to that of the channel

computing the difference. If the number of digits to the right of the decimal of the

reference channel is greater than that of the channel computing the difference, the

reference value below the least significant digit of the channel computing difference is

rounded beforehand.

6.2 Settng the Measurement Channels, Ext. Channels