SECTION 6 - JLG CONTROL SYSTEM

6-8

– JLG Lift –

3121262

Table 6-2. Machine Configuration Programming Information

Configuration Digit

Number

Description

Default

Number

NOTE: The machine configuration must be completed before any personality settings can be changed. Changing

the personality settings first and then changing the model number of the machine configuration will cause
the personality settings to return to default

MODEL NUMBER:
1

0

1

No Model

1500SJ

0
1

ENVELOPE HEIGHT:
2

0

1500SJ: 150' MAX

0

Note: The default settings (bold) will vary depending on the model selection with selection # 5 being the initial default setting.

MARKET:
3

0

1

2

3

4

5

ANSI USA

ANSI EXPORT

CSA

CE

AUSTRALIA

JAPAN

0

ENGINE:
4

1

2

3

4

DEUTZ F4 TIER1: Deutz BF4M1011 Diesel (Tier 1)

DEUTZ F4 TIER2: Deutz BF4M2011 Diesel (Tier 2)

DEUTZ ECM: Engine Control Module

CAT Engine

3

GLOW PLUG:
5

0

1

2

NO GLOW PLUGS: No glow plugs installed.

AIR INTAKE: Glow plugs installed in the air intake on the manifold.

IN-CYLINDER: Glow plugs installed in each cylinder.

2

STARTER LOCKOUT:
6

0

1

DISABLED: Automatic pre-glow time determined by ambient air temperature;
engine start can be attempted at any time during pre-glow.

ENABLED: Automatic pre-glow time determined by ambient air temperature; engine
start is NOT permitted until pre-glow is finished.

0