SECTION 6 - JLG CONTROL SYSTEM
6-76
– JLG Lift –
3121262
10. Hit Enter. The screen will read:
11. Hit enter again. The screen will read:
NOTE: In the following step, a minimum value of 10 must be
indicated on the analyzer before the crack point can
be set. The JLG Control System will not accept a
value less than 10 and the analyzer will not advance
to "CAL COMPLETE" if the crack point is set at a
lesser value.
12. While reading the crack point setting on the ana-
lyzer, activate the Tele Out function until the boom
starts to move or until the crack point setting
reaches a value of 10 if the boom begins to move at
a value lesser than 10, then leave off the control
switch immediately. The display will read CRK PT =
and show the numeric crack point value.
13. Hit enter. The number displayed will be the value
that the crack point is set to. The screen will show: