SECTION 6 - JLG CONTROL SYSTEM

6-22

– JLG Lift –

3121623

6.4 CALIBRATION REQUIREMENT

This machine incorporates a variety of sensors and a high
degree of function interaction. For safety and proper
machine functionality, the calibration procedures must be
repeated for any control module replacement, system cal-
ibration related fault, or removal or replacement of any
sensors, valves, coils.

The chart below lists the calibrations required and poten-
tial reasons for recalibrating.

All calibration procedures are menu driven through the
REMOTE CONTROL.

The user is prompted to exercise the machine in a specific
order to use the machines physical properties to consis-
tently establish sensor response and the interaction of
valves, pumps, and motors.

A REPLACEMENT OF A NEW ECM 1-2 & 3 REQUIRE TO FLASH
THE PROPER MACHINE MODEL SOFTWARE AND TO ADJUST THE
MACHINE SETTINGS. A REPLACEMENT OF A NEW ECM 1-2 DO
NOT REQUIRE THE CALIBRATION OF THE ECM3 AND THE JOY-
STICKS.

Table 6-3. Calibration modules

Calibration

Procedure

Reasons for

Re-calibration

LOAD Cell
Calibration

LSS Module ECM3

replacement

LSS Sensor removal or

replacement

Joystick Calibration

Joystick replacement

Chassis Tilt
Calibration

Master Board ECM1- ECM2

removal or replacement

Tilt indication inaccuracy