SECTION 6 - JLG CONTROL SYSTEM

6-30

– JLG Lift –

3121623

EM.R.C.GND

ON

The stop button on ground remote control is released.

OFF

The stop button on ground remote control is pressed or the ground remote
control is disconnected

ST12 CLOSED

ON

The pressure switch of outriggers 1 and 2 closes the contact – the outriggers are at
end run and the max pressure valve is opened

OFF

The pressure switch contact of outriggers 1 and 2 is opened – the outriggers are
open, partially open or already closed

ST34 CLOSED

ON

The pressure switch of outriggers 3 and 4 closes the contact – the outriggers are at
end run and the max pressure valve is opened

OFF

The pressure switch contact of outriggers 3 and 4 is opened – the outriggers are
open, partially open or already closed

TEMP ALRM A

Option reserved for some

markets

ON

The temperature external probe reached the maximum value – “A” line of the
temperature probe is closed

OFF

The temperature external probe hasn’t reached the maximum value – “A” line of the
temperature probe is open

TEMP ALRM B

Option reserved for some

markets

ON

The temperature external probe reached the maximum value – “B” line of the
temperature probe is closed

OFF

The temperature external probe hasn’t reached the maximum value – “B” line of the
temperature probe is open

POS.1 ARM

ON

The switch of 1-2 arm position is released, contact is close, the 1

st

-2

nd

arm is open

OFF

The switch of 1-2 arm position is pressed, contact is open, the 1

st

-2

nd

arm is closed

TRACK OPEN

ON

Tracks are in wide position. Widening cylinders switches are pressed, contact is
closed

OFF

Tracks are not in full wide position. Widening cylinders switches are released,
contact is open

FREE

Do not consider this signal

EMRG. COMM

ON

The control position key selector for aerial part operation from the ground is
activated (emergency condition)

OFF

The control position key selector for aerial part operation is released (normal
working condition)

MICROROPES

To consider only for

LL20JP - X600AJ

ON

The cables of the extension are OK. The control switch of the cables on extension is
released and the line is closed (normal working condition)

OFF

At list one cable on the extension is out of order. The control switch of the cables on
extension is pressed and the line is open (emergency condition)

START M.TE

ON

The ground button for engine start is pressed

OFF

The ground button for engine start is released

MOTOR TEMP

To consider only for X20JP

- X600AJ

ON

The engine reached the max functioning temperature (emergency condition – the
engine remains at min)

OFF

The engine maintains the correct functioning temperature (normal working
condition)