SECTION 6 - JLG CONTROL SYSTEM
6-108
– JLG Lift –
3121623
DMCC (A) SETTING PROCEDURE:
This procedure is setting the max value of DMCC (A), so
the maximum current that the system require to the bat-
tery charger. This is necessary considering the different
Amps limits in local network of different countries. 48V
pack settings are 18A for 110-120V network and 25A for
220-230V network. 72V pack settings are 13A for 110-
120V network and 30A for 220-230V network.
BE CAREFUL: Selecting the Amps limit and pressing that
button charge setting procedure is starting. The proce-
dure will automatically change the charge limit parameter.
Figure 6-111.
When the process is finished the message below is
appearing.