SECTION 6 - JLG CONTROL SYSTEM

6-56

– JLG Lift –

3121623

SETUP 1 - ACCELER
(CALIBRATING TILT SENSOR)

This menu allows the calibration of the tilt sensor.

A NEW TILT MODULE WILL ACT AS IF IT IS TILTED ALL OF THE
TIME UNTIL THE FOLLOWING PROCEDURE IS PERFORMED.

DO NOT CALIBRATE THE LEVEL SENSOR EXCEPT WITH THE UNIT
LEVELED ON BOTH AXIS. CHECK THE BUBBLE LEVEL TO CON-
FIRM UNIT IS LEVEL (BUBBLE IS IN THE 1° GREEN (CENTER)
AREA).

EXTEND, AND ADJUST THE OUTRIGGERS UNTIL
UNIT IS LEVEL (BUBBLE IS IN THE 1° GREEN (CEN-
TER)
AREA) AND THE TRACKS ARE RAISED OF THE
GROUND

Figure 6-54.

1. Engine OFF.

2. Engine Key Switch ON.

3. Press button 6 "SERVICE"

4. Press button 7 "SETUP“

5. Press button 5 “PASSWORD”

Using the remote control buttons to enter the pass-
word "Level 2": 2857.

NOTE: password above allow to calibrate the TILT SENSOR.

Once the correct password is accepted the display
shown “OK”.

6. Press button 9 “ESC”.

Repeat the above steps if “NO” appear on the dis-
play.

7. Press button 1 “ACCELER” to enter in SETUP TILT

SENSOR.

NOTE: If "ready" --> Go to point 8. If "not ready", mean one or

more outrigger not tach the ground or photocell not
aligned.

8. Press Button 1 to reset the TILT.

Check the values if both axle showed in the display
become zero, otherwise press button 1 again until both
values are zero.

Press 3 times button 9 to Esc to escape.

NOTE: Using the password "Level 3" 4658 to read the values

only