background image

4

Technical data

4.2

Protective insulation

18

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Example
Which type of protective insulation is used between the bus terminal of the device module in slot

MXI1 or MXI2 and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.

• The separate potential area of the bus terminal of the device module has a "basic insulation".
• The separate potential area of the mains terminal has a "reinforced insulation".

Result: The insulation between the X100 mains terminal and the bus terminal is of the "reinforced

insulation" type.