Ethercat: error: lenze setting loaded [0x00c86420, Ethercat: quit 'operational' state [0x00c88131, Ethercat: sync loss detected with standard device – Lenze E94AYCET User Manual

Page 93: 0x00c88132, 0x00c86420, 0x00c88131, 12 error messages

Advertising
background image

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

93

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EtherCAT: Error: Lenze setting loaded [0x00c86420]

EtherCAT: Quit 'Operational' state [0x00c88131]

EtherCAT: Sync loss detected with standard device [0x00c88132]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access via standard device to parameter set in the

memory module was not successful.

Repeat download of the application (including module).

Response (Lenze setting printed in bold)

Setting:

C13880/1

/

C14880/1

( Configurable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The EtherCAT data exchange was stopped in the

"Operational" state.

See also chapter "

Interruption of EtherCAT

communication

"

( 81)

.

• Check cables and terminals.

• The master has to reset the node to the "Operational"

status. (If required, check a pending emergency

message first).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• The cycle time settings are faulty.

• The task time setting of a linked PLC program is faulty.

• EtherCAT master / DC master settings are incorrect.

• The sync source setting is faulty.

• Check the cycle times.

• Check the task time of a linked PLC program.

• Check the EtherCAT master / DC master settings.

• Check the settings of the standard device in

C01120

(selection of the sync source).