C00637 | resp. to new module in mxi2, C01120 | sync source, C01501 | resp. to comm. error with mxi1 – Lenze E94AYCET User Manual

Page 95: C01120, C01501, Module in slo, 13 parameter reference

Advertising
background image

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

95

13

Parameter reference

13.1

Communication-relevant parameters of the standard device

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00637

C01120

C01501

Parameter | Name:

C00637 | Resp. to new module in MXI2

Data type: UNSIGNED_32

Index: 23939 = 0x5D83

Response when a new module has been inserted in module slot 2 of the standard device.
Selection list

(Lenze setting printed in bold)

1 Error
6 Information
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C01120 | Sync source

Data type: UNSIGNED_8

Index: 23455 = 0x5B9F

Selection of the source for DC synchronisation signals.

• Depending on the slot in the standard device, set the selection "4: Module in MXI1" or "5: Module in MXI2" for

the communication module.

• In general, only one source can synchronise the drive.

Synchronisation with "Distributed Clocks" (DC) ( 35)

Selection list

(Lenze setting printed in bold)

0 Off
1 CAN on board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1

... ...

13 Digital input 8

Read access  Write access  RSP  PLC-STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01501 | Resp. to comm. error with MXI1

Data type: UNSIGNED_32

Index: 23074 = 0x5A22

Response to a communication error between an "intelligent" module in module slot 1 and the standard device
Selection list

(Lenze setting printed in bold)

0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
5 Warning

Read access  Write access  CINH  PLC-STOP  No transfer

Advertising