2 reading and writing parameters, Reading and writing parameters, 9parameter data transfer – Lenze E94AYCET User Manual

Page 69

Advertising
background image

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

69

9

Parameter data transfer

9.2

Reading and writing parameters

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Reading and writing parameters

Parameters ...

• for instance are set for one-time system settings or if materials are changed within a machine;
• are transmitted with a low priority.

In the case of Lenze drive, the drive-specific parameters to be changed are contained in codes or in

case of the CANopen device profile "CiA402" as device profile objects.

Indexing of the Lenze codes
If they are accessed via a communication module, the codes of the drive are addressed by the index.
The index of Lenze code numbers within the manufacturer-specific area of the object directory is

between 8192 (0x2000) and 24575 (0x5FFF).

Structure of a mailbox datagram
Mailbox data are transmitted in a datagramm within an EtherCAT frame. The data area of the

mailbox datagram has the following structure:

Conversion formula
Index [dec]

Index [hex]

24575 - Lenze code

0x5FFF

- Lenze code

hex

Example of C00002 (device commands)
Index [dec]

Index [hex]

24575 - 2 = 24573

0x5FFF - 2 = 0x5FFD

Mailbox

Header

CoE

Header

SDO control

byte

Index

Subindex

Data

Data

6 bytes

2 bytes

1 byte

2 bytes

1 byte

4 bytes

1 ... n bytes