4technical data – Lenze E94AYCET User Manual

Page 20

Advertising
background image

4

Technical data

4.4

Communication time

20

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

The mentioned basic conditions result in the following processing times for the process data in the

drive:

• DC use (synchronised operation):

The processing time starts with the acceptance of the setpoints by the drive with the Sync0

event (DC synchronisation cycle) and ends with the provision of the current actual values in the

EtherCAT interface.
Depending on the selected

Process data mode

( 39)

(

C13892

/

C14892

), the following

processing times result:

• Deterministic mode: 2.1 ms + interval time of the application task
• Optimised mode: 1.3 ms + interval time of the application task

• No DC use (non-synchronised operation):

The processing time starts with the acceptance of the setpoints by the drive at a time that is not

synchronised with the EtherCAT master and ends with the provision of the current actual values

in the EtherCAT interface.
The following processing time arises:
1.3 ms + 1.0 ms (tolerance) + interval time of the application task

Documentation of the 9400 function library
Here you can find detailed information on how to set the interval time of the application

task.

Advertising