Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

61

8

Process data transfer

8.1

Configuring process data (PDO mapping)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.1.1

Setting PDO mapping with the »Engineer«

With Servo Drives 9400 you can arrange the process data individually. For this purpose, the

»Engineer« provides a port configurator.

The following example describes the steps required for the Servo Drive 9400 HighLine to implement

process data communication with a controller (EtherCAT master) during which a control/status

word and a 32-bit setpoint/actual value is exchanged, respectively.

How to set the PDO mapping with the »Engineer«:

1. The process data mapping to the port variables is executed in the »Engineer« under the

Process data objects tab of the corresponding fieldbus communication module:

2. Select the receive object PDO_RX0:

Note

The port mapping is not a configuration, which can be carried out online for the Servo

Drive 9400 HighLine. For this purpose, the »Engineer« project must be updated and then

the application must be downloaded.