Before communication is possible via EtherCAT, the fieldbus passes through the EtherCAT state

machine during start-up. The following illustration depicts the possible state changes from the

point of view of an EtherCAT slave:

[7-1]

EtherCAT state machine

The current status of the EtherCAT state machine is shown in

C13861

/

C14861

and is indicated via

the RUN LED.

E94AYCET009

Operational

Pre-Operational

Init

Safe-Operational

State

Description

Init

• Initialisation phase

• No SDO/PDO communication with the slaves

• Device detection possible by means of a fieldbus scan

Pre-operational

• The fieldbus is active.

• SDO communication (mailbox communication) is possible.

• No PDO communication

Safe-operational

• SDO communication (mailbox communication) is possible.

• PDO communication:

• The input data in the process image are updated.

• The output data from the process image are not transferred to the slaves.

Operational

Normal operation:

• SDO communication

• PDO communication

• Fieldbus synchronisation successful (if used)

Note!

• A fieldbus scan can be carried out during any EtherCAT status.
• SDO communication via the EtherCAT bus is only possible if at least the "Pre-

Operational" state has been reached.

• Only in the transitional phases between states can bus nodes be in different states.