5.2

Electrical installation

5.2.1

EMC-compliant wiring

In typical systems, standard shielding is sufficient for Ethernet cables.
However, in environments with a very high level of interference, EMC resistance can be improved

by earthing both sides of the cable shield as well.
For this purpose, observe the following notes:

1. The distance of the additional earthing from the Ethernet plug depends on the slot of the

module. The distance is:

• approx. 10 cm for the upper slot (MXI1)
• approx. 20 cm for the lower slot (MXI2)

2. Measure the appropriate distance along the cable and, starting from this point, remove 2 cm of

the cable's plastic sheath.

3. Fasten the cable shield to the shield sheet of the Servo Drive 9400.

[5-3]

EMC-compliant wiring

Documentation for the standard device, control system, plant/machine
Observe the notes and wiring instructions stated.

E94YCXX008

A Fastening to the shield sheet of the Servo Drive

9400

B Outgoing EtherCAT line at X247 (OUT)

C IncomingEtherCAT line at X246 (IN)

D Communication module in slot MXI1 of the

Servo Drive 9400